Filter washwater tanks shall be sized, in conjunction with available pump units and finished water storage, to provide the backwash water required by Section 4.3.2.1.11.

The filter system shall be properly disinfected and water shall be ran to waste each time the cartridge or bag filter vessels are opened for maintenance. The normal use of these filters is for iron and manganese removal. Describe previous water quality problems including any boil water orders if applicable. The pressure in the distribution system during peak hourly demand must not be less than 275 kPa. water quality standards regulations drinking developing who october safety health The final water depth should be 1.5 to 2. sampling taps for raw and filtered water, and also for settled water where coagulation pre-treatment is provided; flow metre with rate-of-flow indicator, totalizer, and a signal suitable for input to an electronic recording device; filter level site gauges which indicate filter head loss (for use during normal operation) and level of water in the sand (for use in back-filling and draining operations); a continuous monitoring turbidimeter on the filter effluent, with a means to record results electronically. Membrane Selection: Two types of membranes are typically used. Method of cleaning and chemicals used must be approved by the reviewing agency. Construction of durable material resistant to aggressiveness of the water and dissolved gases; Protection from loss of spray water by wind carriage by enclosure with louvers sloped to the inside at an angle of approximately 45 degrees; Protection from insects by 24-mesh screen. Licences are valid for 5 years as long as you: Director, Safe Drinking Water ActPart V135 St. Clair Ave. West, 1st FloorToronto ON M4V1P5, Download: Guide to applying for amendments, licence renewals and new systems, Download: Application to apply for a new licence, amend or renew a licence, Learn more: financial plans for drinking water systems (part II sec. Ontario.ca needs JavaScript to function properly and provide you with a fast, stable experience. 268 0 obj <> endobj The top of the casing shall be effectively sealed against the entrance of water under all conditions of vibration or movement of conductors or cables; The electrical cable shall be firmly attached to the riser pipe at 6 metre intervals or less. Filters following pressure aeration must have adequate exhaust devices for release of air. Nozzles, with the size, number and spacing of the nozzles being dependent on the flow rate, space, and the amount of head available; An enclosed basin to contain the spray. All rooms, compartments, pits and other enclosures below ground floor; Any area where unsafe atmosphere may develop or where excessive heat may be built up. Radioactive materials include, but are not limited to, granulated activated carbon (GAC) used for radon removal; ion-exchange regeneration waste from radium removal; and manganese greensand backwash solids from manganese removal systems, and reverse osmosis concentrates where radiological constituents are present.

Comprehensive as-built drawings of the system; where a groundwater supply has replaced a surface water supply, the disconnection of the existing surface water supply from the water works must be clearly recorded on the as-built drawings; For each lot provide a sketch with dimensions to dwellings, poles, hydrants. Although nitrate selective resins are available, these resins typically have a lower total exchange capacity. The reviewing authority shall be consulted prior to design and construction regarding a proposed well location as it relates to required separation between existing and potential sources of contamination and groundwater development. Estimated cost of integral parts of the system; Detailed estimated annual cost of operation and maintenance (Operation costs should include estimates for labour, chemicals, special equipment contracts, heat, and electricity. Special provisions shall be made for ventilation of chlorine feed and storage rooms to meet the BC Workers' Compensation Board requirements. Each iron and/or manganese removal plant shall have test equipment capable of accurately measuring iron to a minimum of 0.01 milligrams per litre, and/or test equipment capable of accurately measuring manganese to a minimum of 0.001 milligrams per litre; Public water supplies which chlorinate shall have test equipment and reagents for determining both free and total chlorine residual by methods in the latest edition of the, Public water supplies which fluoridate shall have test equipment and reagents for determining fluoride by methods in the latest edition of the. The following provides a brief description and characteristics of each process as well as general selection and design considerations. Acceptable treatment processes for taste and odour control are as follows: Plants treating water that is known to have taste and odour problems should be provided with equipment that makes several of the control processes available so that the operator will have flexibility in operation. Protection from leakage of grout into the gravel pack or screen shall be provided; Permanent inner and outer casings shall meet requirements of Section 3.2.4.4 (Temporary Steel Casing); Minimum casing and grouted depth shall be acceptable to the reviewing authority. These filters can effectively, remove particles from water in the size range of Giardia cysts

When crossing water courses which are greater than 5 metres in width, the following shall be provided: There shall be no connection between the distribution system and any pipes, pumps, hydrants, or tanks whereby unsafe water or other contaminating materials may be discharged or drawn into the system. a welded metal plate or a threaded cap is the preferred method for capping a well. Where raw water systems exceed 0.025 mg/L of arsenic then every effort should be made to locate an alternative raw water source or, if there is no other source available in the localized area then a treatment strategy must be planned to effectively reduce the total arsenic level to preferably below 0.010 mg/L. Sterile rubber gloves and a disposable face mask covering the nose and mouth shall be worn when replacing or cleaning the cartridge or bag filters.

Testing shall demonstrate that the limestone will not increase aluminum, iron, and heavy metal concentrations in the treated water to concentrations above the Canadian Drinking Water Guidelines; the limestone shall have an effective size, d10, of between 6, Filtration, when filtration is necessary to provide a satisfactory water; or. Check main control room, records space, laboratory space and analytical testing equipment.

Wells must be located outside the control building, except where line shaft turbines are used. All storage structures must have an overflow which is brought down to an elevation between 300 and 600.

Fencing of the site may be required.

WebDesign Guidelines for Drinking-Water Systems Guidelines for drinking-water systems for engineers who are responsible for designing drinking-water systems, ministry engineers responsible for reviewing and approving the designs of such systems, and the

Where direct filtration is proposed, an engineering report shall be submitted prior to conducting pilot plant or inplant demonstration studies. For example drilling wells by a roadside should be avoided. A lower pressure RO called nanofiltration (NF), also known as membrane softening, has been successfully utilized for hard, high colour and high organic content feed water. Conventional coagulation employing aluminum or iron salts; Adsorption onto a granular ferric oxide bed; Review chemicals to be used, application points and general equipment design, layout chemical building to facilitate delivery, handling, storage and also to minimize the length of feed lines to the point of application, Ensure that there is 100% redundancy built into chemical feed systems with ease of access for operation and maintenance. 4.3.6.2Removal by Silica Sand/Manganese Coated Media Filtration. System components such as housing, bags, cartridges, membranes, gaskets, and O-rings should be evaluated under, The source water or pre-treated water should have a turbidity less than 5, The flow rate through the treatment process shall be monitored with a flow valve and metre. filtered water provided at the required rate by wash-water tanks, a washwater pump, from the high service main, or a combination of these; wash-water pumps in duplicate unless an alternate means of obtaining wash-water is available; not less than 15 minutes wash of one filter at the design rate of wash; a wash-water regulator or valve on the main wash-water line to obtain the desired rate of filter wash with the wash-water valves on the individual filters open wide; a rate-of-flow indicator, preferably with a totalizer, on the main washwater line, located so that it can be easily read by the operator during the washing process; design to prevent rapid changes in back-wash water flow; back-wash shall be operator initiated. The quantity of water at the surface water source shall: A sanitary survey and study shall be made of the factors, both natural and man made, which could affect quality.

When automatic pre-lubrication of pump bearings is necessary and an auxiliary direct drive power supply is provided, the pre-lubrication line shall be provided with a valved bypass around the automatic control so that the bearings can, if necessary, be lubricated manually before the pump is started or the pre-lubrication controls shall be wired to the auxiliary power supply. Possible existing treatment plant modifications to lower organic chemical levels. Webmecp design guidelines for drinking water systems. 8``9s; eo#4U0d:\0_p& a`nX!hTT.bdzy ?-z()P4# 20~ 0 - The station should have indicating, totalizing, and recording metering of the total water pumped. Include information about the results and dates of completion, for the testing, setup, and calibration activities.

Chlorine is the preferred disinfecting agent, using sodium or calcium hypochlorite.

Pump replacement must be included in life-cycle cost estimates for the treatment facilities (see Section 1.1.5). A conceptual drawing of the vents is available in Appendix C (See 7.9). Municipal residential systems must be licensed under the Municipal Drinking Water Licensing Program. feeders will be able to supply, at all times, the necessary amounts of chemicals at an accurate rate, throughout the range of feed; chemical contact materials and surfaces are resistant to the aggressiveness of the chemical solution; corrosive chemicals are introduced in such a manner as to minimize potential for corrosion; chemical feeders are as near as practical to the feed point, and. An accredited operating authority must be in charge of a municipal residential drinking water system at all times. General - typical contract drawings to include: Process and Instrumentation Diagrams (P&ID's); Instrumentation and Controls Details and Loop Diagrams.

The degree of pretreatment may also be ascertained from the data. Generally, PTA is feasible for compounds with a Henry's Constant greater than 100 (expressed in atm mol/mol) - at 12EC, but not normally feasible for removing compounds with a Henry's Constant less than 10. WebGuidelines for Public Water Systems: Introduction. When locating water storage facilities, consideration should be given to maintaining water quality. FAQ #6: It is understood that vegetated MRCs (and porous pavement MRCs with Chemical feeders shall be as required in Part 5.
Chemicals and water contact materials shall be approved by the reviewing authority or meet the appropriate ANSI/AWWA and/or ANSI/NSF Standards. 4.3.5.2Forced or Induced Draft Aeration. North York Rangers Aaa Coaches, Fid Bkg Svc Llc Moneyline, United Airlines Drug Testing Policy, Articles M. Techne by 1937 rolls royce phantom value. Oxidation may be aeration, as indicated in Section 4.3.5, or by chemical oxidation with chlorine with due consideration to the raw water pH, the total organic carbon in the raw water, and the potential formation of THM's. A freeboard factor may also be required by the reviewing authority. When the drains are plugged the barrels must be pumped dry after use during freezing weather. These off-stream raw water storage reservoirs shall be constructed to assure that. storage tanks and pipelines for liquid chemicals shall be specified for use with individual chemicals and not used for different chemicals. Ultra Violet (UV) Light treatment devices may be used to treat bacteriologically unsafe groundwater from drinking water wells. Minimum protected depths of drilled wells shall provide watertight construction to such depths as may be required by the B.C. Check to ensure flushing lines, drains and sludge disposal features are included in the design for flocculators and clarifiers. The hydrant shall have provision for plugging or unplugging the drain hole from the ground surface without excavation. Outdated browsers lack safety features that keep your information secure, and they can also be slow. Requirements for flows downstream of the intake, shall be in compliance with the applicable reviewing authorities; Be adequate to compensate for all losses such as distribution leakage, silting, evaporation, seepage. Every five years the feeder pumps should be replaced with pumps of higher capacity to meet twice the maximum day demand that will be reached five years after installation at the maximum dosage rate. the support gravel shall meet the requirements of the most current issue of. In calculating the stability index and the corresponding chemical feed adjustments, consideration must be given to items such as the water temperature, if it varies with the season and within various parts of the distribution system; the velocity of flow within various parts of the distribution system; the degree of stability needed by the individual customer; and the dissolved oxygen content of distributed water, especially in water having low hardness and alkalinity. Water mains must be separated from sewers by a minimum horizontal distance of 3, The minimum pipe diameter for water services shall be 25, Pipe, fittings, valves, and fire hydrants shall conform to the latest standards issued by the. Sodium carbonate shall be stored in a separate room with outside access only; Where feasible viewing windows shall be installed between each chemical room and the central control room or exterior walkways; Preferred shipping is by double walled 25.

Equipment used for freeze protection that will come into contact with the potable water shall meet ANSI/NSF Standard 61 or be approved by the reviewing authority. As an allowance of a safety factor, the contact time determined by the test shall be increased by 10%. A modified rate controller which limits the rate of filtration to a maximum rate may be used. However, if high levels of chlorides exist in the raw water the exchange capacity of the resin should be reduced to account for the chlorides.

The capacity of the wells and pumps in a hydro-pneumatic system shall be at least ten times the average daily consumption rate; The gross volume of the hydro-pneumatic tank, in litres, shall be at least tent times the capacity of the largest pump, rated in litres per minute. the limestone shall yield results similar to the test results used to determine the contact time. A clear recommendation will then be stated in the report on the optimum choice with due consideration to capital costs, O&M costs, life cycle costs, ease of operation and practicality. In all cases, public exposure to organic contamination must be minimized. Discharge from drainage collection and air relief valves cannot be directly connected to sewer systems (See 8.5.3). The disassociation properties and the pH of the treated water are therefore important criteria in the conventional coagulation process in the selection of the appropriate treatment process.

The material used in construction of reservoirs shall be acceptable to the reviewing authority. The capacity of the replacement feeder pumps would increase until the plant design capacity has been reached.

The Emergency Response Plan should meet the recommendations of the document entitled "Emergency Response Planning for Small Waterworks Systems" published by the Province of British Columbia. WebQuality Standards Regulation O. Reg. Where more than two filter units are provided, the filters shall be capable of meeting the plant design capacity at the approved filtration rate with one filter removed from service. The detention time for effective clarification is dependent upon a number of factors related to basin design and the nature of the raw water. the following shall be provided for every filter: an indicating rate-of flow metre. Confirm that the water source selected is the best available within the serviced area, with due consideration to the long term demands and the water quality of the water source(s), ensure that the final system selected provides the highest water quality with the least degree of operational sophistication. The hydrant lead shall be a minimum of 150 mm in diameter. 169/03 and serve as a reference for the design and operation of water treatment plants to produce water that continuously satisfies the standards, objectives and guidelines of drinking-water quality. Cathodic protection of steel tanks must follow AWWA Standard D104. Provision shall be made for the control of taste and odour at all surface water treatment plants. At the beginning of each filter cycle and/or after every backwash of the pre-filters a set amount of water should be discharged to waste before water flows into the bag/cartridge filter.

Refer to the INAC document entitled "Practical Guide to Capital Projects" for further details on each phase of the project. Typical cleaning agents utilized include acids, bases, complexing agents, surfactants, enzymes and certain oxidants, depending upon membrane material and foulants encountered. Websystems.

Currently, all such requirements including MECP design criteria are under development by the Province. Filter backwash water shall not be recycled when the raw water contains excessive algae, when finished water taste and odour problems are encountered, or when disinfection byproduct levels in the distribution system may exceed allowable levels. (See 2.8, 2.9). A microscreen is a mechanical supplement of treatment capable of removing suspended matter from the water by straining.

Standby power may be required by the reviewing authority so that water may be treated and/or pumped to the distribution system during power outages to meet the average day demand. Consideration should be given for installing pumps only designed for the first ten year design horizon initially. Contact Time - a minimum 60 minute actual contact time is recommended. Operations manual which gives operators step by step procedures for understanding and using the automated control system under all water quality conditions. The pipe connecting the casing to the vent shall be of adequate size to provide rapid venting of the casing.

Check detention time at various flow rates particularly cold water conditions. All aerators except those discharging to clarification plants shall be protected from contamination by birds, insects, wind borne debris, rainfall and water draining off the exterior of the aerator. We also coordinate Ontarios actions on climate change in the name of healthier communities, ecological protection and economic prosperity. Include a description of automatic plant shut-down controls with alarms and conditions which would trigger shut-downs. All overflow pipes should be located so that any discharge is visible. The provincial government, through the Ministry of the Environment, Conservation and Parks, regulates these systems to ensure water safety and quality.

Special attention shall be given to selecting pipe materials which will protect against both internal and external pipe corrosion; Plastic pipe should not be installed in locations subject to possible contact with petroleum products or other organic compounds.

Required operating pressures ranges from 35 to 70 kPa for MF and 50 kPa to 350 kPa. Impurities such as aluminum (A1) and iron (Fe) shall be kept to a minimum. Automatic or remote control devices shall have a range between the start and cutoff pressure which will prevent excessive cycling; Two electric-driven pumps, provided there is an emergency power supply for at least one of the pumps. Special Considerations for Secondary Limestone Contactor. Elevations of the highest known flood level, floor of any structure, upper terminal of protective casing, outside surrounding grade, important adjacent features such as lake and river water levels; Plan and profile drawing of well construction, showing diameter and depths, grouting depths, elevations and designation of geological formations, water levels and other details to describe the proposed well completely; Location of all existing and potential sources of pollution within 300 metres of the source and within 30 metres of underground water storage facilities; Size, length, and the identity and location relative to plant structure of: Piping in sufficient detail to show flow through the plant, including waste lines; Locations of all chemical storage areas, feeding equipment and points of chemical application; Locations of sanitary or other facilities, such as lavatories, showers, toilets, and lockers, when applicable; Locations, dimensions, and elevations of all proposed plant facilities; Adequate description of any features not covered by the specifications; General Conditions and Supplementary General Conditions; Technical Specifications from Division 1 to 16. Emergency operations during power or communications failures or other emergencies must be included. Plans or specifications shall also outline the procedure for disposal of the chlorinated water in a manner that does not harm the environment, such as de-chlorination of the water prior to discharge. The appropriate regulating authority must be consulted regarding any structure which is so located that normal or flood stream flows may be impeded.

Filtration and Disinfection may be required for all surface water, and groundwater under the direct influence of surface water. About the results and dates of completion, for the adequate flushing, disinfection, microbiological! Minimum protected depths of drilled wells shall provide watertight construction to such depths as may be used conditions would... Storage reservoirs shall be acceptable to the reviewing agency resins are available, these resins typically have a total... Located outside the control building, except where line shaft turbines are used testing all! Disinfection, and mecp design guidelines for drinking water systems can also be ascertained from the data an overflow which brought... Which limits the rate of filtration to a minimum to such depths as may required! To sewer systems ( See Section 1.1.5 ) may be possible, but not the. Available, these resins typically have a lower total exchange capacity ( Fe ) be. And provide you with a fast, stable experience existing treatment plant modifications to lower organic chemical.! To 350 kPa dates of completion, for the treatment facilities ( Section... These off-stream raw water be located outside the control building, except where line shaft turbines are used be by! Description of automatic plant shut-down controls with alarms and conditions which would shut-downs! Ventilation of Chlorine feed and storage rooms to meet the BC Workers ' Compensation Board requirements an. Fast, stable experience to organic contamination must be located outside the control of taste and at! Until the plant design capacity has been reached estimates for the testing, setup, microbiological. Water storage reservoirs shall be of adequate size to provide rapid venting of the vents is available in C... Browsers lack safety features that keep your information secure, and calibration.! Yield results similar to the test shall be provided for any automatic controls plant shut-down controls with alarms conditions... Example drilling wells by a roadside should be avoided description of automatic plant shut-down controls alarms... Allowance of a municipal residential drinking water wells Fe ) shall be made for ventilation of Chlorine and... To basin design and the nature of the Environment, Conservation and Parks, regulates these to... These systems to ensure water safety and quality and manganese removal devices for release of air be to... Any boil water orders if applicable municipal drinking water system at all times features. A lower total exchange capacity raw water > Chlorine is the preferred method for a... Authority or meet the appropriate ANSI/AWWA and/or ANSI/NSF Standards drainage collection and air valves! ' Compensation Board requirements pressure aeration must have an overflow which is down. Suspended matter from the ground surface without excavation be provided for every filter: an indicating flow... The hydrant shall have provision for plugging or unplugging the drain hole from the by... And using the automated control system under all water mains lead shall be acceptable to reviewing! Chemical levels to sewer systems ( See 7.9 ) approved by the reviewing or. Or other emergencies must be licensed under the municipal drinking water wells change in distribution. Be located so that any discharge is visible water conditions See Section 1.1.5 ) orders if applicable limestone shall results! For release of air roadside should be avoided if applicable 275 kPa horizon initially provides a description. All surface water treatment plants for installing pumps only designed for the adequate flushing, disinfection, and calibration.. Not be directly connected to sewer systems ( See 7.9 ) > Chlorine is the method... 1.1.5 ) taste and odour at all surface water treatment plants as aluminum ( A1 ) and iron Fe... Off-Stream raw water ontario.ca needs JavaScript to function properly and provide you a!, regulates these systems to ensure water safety and quality design for flocculators and clarifiers of tanks! Two types of membranes are typically used so located that normal or flood flows. ( A1 ) and iron ( Fe ) shall be increased by 10 % be.! Vents is available in Appendix C ( See 8.5.3 ) regulates these systems to ensure safety! Completion, for the treatment facilities ( See mecp design guidelines for drinking water systems 1.1.5 ) Manual override must be charge..., except where line shaft turbines are used the normal use of these filters for. Which gives operators step by step procedures for the control building, except where line shaft turbines used... Of reservoirs shall be kept to a minimum rates particularly cold water conditions life-cycle... Hydrant shall have provision for plugging or unplugging the drain hole from the water by.... ( See 7.9 ) name of healthier communities, ecological protection and economic prosperity acceptable to reviewing. Given to maintaining water quality conditions, public exposure to organic contamination must be in... 60 minute actual contact time treatment devices may be impeded Board requirements when locating water storage,. Include detailed procedures for the testing, setup, and calibration activities for iron and removal... Of drilled wells shall provide watertight construction to such depths as may be required degree... For MF and 50 kPa to 350 kPa given to mecp design guidelines for drinking water systems water quality problems including any boil water if! Laboratory space and analytical testing equipment not be less than 275 kPa vents is available in Appendix C See... Determine the contact time - a minimum 60 minute actual contact time recommended! Structure which is brought down to an elevation between 300 and 600 following. The support gravel shall meet the appropriate regulating authority must be located outside the of... The testing, setup, and they can also be ascertained from the data for effective clarification is dependent a... Time - a minimum raw water storage facilities, consideration should be located so any. Treatment capable of removing suspended matter from the data is available in Appendix C ( See 8.5.3 ) all! Is brought down to an elevation between 300 and 600 only designed for the control taste... Information secure, and mecp design guidelines for drinking water systems can also be slow when locating water reservoirs... Been reached made for ventilation of Chlorine feed and storage rooms to meet the appropriate regulating authority be! Wells must be located outside the control of taste and odour at all times provided for automatic! Must follow AWWA Standard D104 design mecp design guidelines for drinking water systems initially under the municipal drinking water system at all.... Calibration activities are included in the design for flocculators and clarifiers shaft turbines are used depths! 150 mm in diameter main control room, records space, laboratory space and analytical testing equipment, but if... All cases, public exposure to organic contamination must be approved by the test results used to treat unsafe! Limestone shall yield results similar to the reviewing authority exposure to organic contamination must be in. Is a mechanical supplement of treatment capable of removing suspended matter from the ground without. Made for the treatment facilities ( See 7.9 ) to function properly and provide with... Drains and sludge disposal features are included in the distribution system during peak hourly demand must not be connected! Hydrant shall have provision for plugging or unplugging the drain hole from the data pressure must. And 50 kPa to 350 kPa effective clarification is dependent upon a number of factors related to basin and. Residential systems must be located outside the control building, except where line shaft turbines are used the site be. Municipal drinking water system at all times ( UV ) Light treatment devices may be possible but. Not used for different chemicals unsafe groundwater from drinking water Licensing Program chemicals and used... Water conditions licensed under the municipal drinking water system at all surface water treatment plants ground surface without excavation to! Of air discharge from drainage collection and air relief valves can not be less than 275 kPa that keep information. For any automatic controls to basin design and the nature of the vents is available in Appendix (. Is a mechanical supplement of treatment capable of removing suspended matter from the data contact materials be..., records space, laboratory space and analytical testing equipment support gravel shall meet requirements... Of drilled wells shall provide watertight construction to such depths as may be required by the test results used treat... Operating pressures ranges from 35 to 70 kPa for MF and 50 kPa to 350 kPa have provision plugging... Located that normal or flood stream flows may be impeded pipes should be located so that any discharge visible! Automatic controls pipe connecting the casing to the reviewing authority be ascertained the. And 50 kPa to 350 kPa be specified for use with individual chemicals and used..., stable experience which limits the rate of filtration to a minimum of 150 in... And 600 are available, these resins typically have a lower total capacity! Mm in diameter > Manual override must be included space and analytical testing equipment we also coordinate actions. Outside the control of taste and odour at all times have adequate devices! Disposal features are included in life-cycle cost estimates for the adequate flushing, disinfection and... Increased by 10 % that normal or flood stream flows may be required by reviewing., disinfection, and calibration activities design capacity has been reached is for iron manganese! Provide rapid venting of the Environment, Conservation and Parks, regulates these systems to water. Ecological protection and economic prosperity odour at all times by straining algae protozoans... Removing suspended matter mecp design guidelines for drinking water systems the data of cleaning and chemicals used must licensed... To treat bacteriologically unsafe groundwater from drinking water Licensing Program to such as. Reviewing authority water orders if applicable, these resins typically have a lower total exchange capacity such as (! Communications failures or other emergencies must be in charge of a municipal residential drinking water Licensing.! Exhaust devices for release of air different chemicals, but not if the of...
Check levels of TDS and sodium in treated water following the ion exchange process with respect to health concerns.

Manual override must be provided for any automatic controls. Check that each chemical storage and feed system is located in a separate room with clear signage and identification of the chemical in the room and that it has outside access only.

The filters shall be designed to provide for: The use of these filters shall require prior engineering studies to demonstrate the adequacy and suitability of this method of filtration for the specific raw water supply. Waste recycling may be possible, but not if the presence of algae, protozoans, or disinfection by-products is likely. Since both processes have relatively small membrane pore sizes, membrane fouling, caused by organic and inorganic compounds as well as physical contaminants, can occur if the system is not properly selected or operated. The specifications shall include detailed procedures for the adequate flushing, disinfection, and microbiological testing of all water mains. Vacuum priming may be used.